SCADA ModbusTCP

Water Roster integrates ModbusTCP for easy integration into site level control systems. This enables easy operation as a simple IO module manually turning on/off each solenoid valve, remote monitoring of the solenoid valve state as well as remote control over the running schedule. For connection options see the device specifications page.

​

Function

0x1, 0x5 and 0xF (Read/Write coils)

Register

Description

0000 (1) 

Zone1 Active (0=0ff, 1=On). Overwritten when auto-mode is set (1)

Default ID

1

0001 (2) 

Zone1 Auto (0=Manual, 1=Auto)

0010 (11) 

Zone2 Active (0=0ff, 1=On). Overwritten when auto-mode is set (1)

0020 (21) 

Zone3 Active (0=0ff, 1=On). Overwritten when auto-mode is set (1)

0011 (12) 

Zone2 Auto (0=Manual, 1=Auto)

0021 (22) 

Zone3 Auto (0=Manual, 1=Auto)